The MTL4511 is a single-channel switch/proximity detector interface isolator under Eaton, featuring line fault detection (LFD) functionality. It is mainly designed for use in hazardous environments. Below is its detailed information:
- Complies with standards GB/T 3836.1-2021 and GB/T 3836.4-2021 (Chinese national standards for explosive atmospheres).
- Certified to CNCA-C23-01:2019 Implementation Rules for Compulsory Product Certification - Explosion-Proof Electrical Equipment (mandatory certification for explosion-proof electrical products in China).
Single channel (designed for one-to-one signal connection with a single switch or proximity detector).
- Switch Installation Location: Suitable for hazardous areas of Zone 0, IIC, T6 (Zone 0: continuous/long-term presence of explosive gas mixtures; IIC: high-level explosion risk for gas groups; T6: highest temperature class, up to 85°C surface temperature).
- Proximity Detector Installation Location: Suitable for hazardous areas of Zone 0, IIC, T4-T6 (if properly certified), as well as Div.1, Group A hazardous locations (Div.1: explosive mixtures may exist under normal operating conditions; Group A: highest risk for flammable gases like acetylene).
- Input compatibility: Supports proximity switches (NAMUR type) conforming to the BS EN 60947-5-6:2001 standard (NAMUR is a common specification for sensors in explosive environments).
- Sensor voltage supply: Provides 7-9V DC voltage through a 1kΩ±10% resistor (powers the field proximity switch).
- Phase: Normal phase.
- Switching logic:
- Output closes when input current > 2.1mA (input circuit resistance < 2kΩ).
- Output opens when input current < 1.2mA (input circuit resistance > 10kΩ).
- Hysteresis: Nominal 200µA (equivalent to 650Ω, prevents frequent switching due to minor signal fluctuations).
- Selection: Users can enable/disable or configure LFD via a switch on the side of the device.
- Fault response: When an input line fault is detected, the channel’s output relay de-energizes, and the LED indicator illuminates (for visual fault alerts).
- Fault thresholds:
- Open-circuit alarm: Activates when input current < 50µA; deactivates when > 250µA.
- Short-circuit alarm: Activates when input resistance < 100Ω; deactivates when > 360Ω.
- Output type: Relay output.
- Contact rating:
- 10W, 0.5A at 35V DC;
- 2A at 250V AC (with power factor cosø > 0.7);
- 2A at 40V DC (resistive load).
Maximum 10ms (ensures rapid signal transmission between hazardous and safe areas).
- Voltage range: 20-35V DC.
- Current consumption: Maximum 25mA at 24V DC (low power consumption for system efficiency).
Approximately 0.22 lbs (about 99.8g, lightweight for easy installation in control cabinets).
- Phase inversion: A switch on the module’s side allows users to select channel phase inversion (adapts to different control system logic requirements).
- Functional safety: These operating modes have been evaluated and are suitable for IEC 61508 functional safety applications (ensures reliability in safety-critical systems).